aa

    aa

    SIBA
    3017814.100.0
    Product available on request

    Product Request:


    aa

    aa

    do not include special characters

    * Required fields

     

    Class
    HH Back up
    Rated current In (A)
    100
    Rated Voltage Un AC (V)
    17500
    Rated break.capacity I1 AC (A)
    63000
    Voltage of total I2t test
    15225
    Format
    Cylindrical
    Dimension
    85x367mm
    Pre-arcing I2t value (A2s)
    28000
    Total I2t value (A2s)
    199000
    Homologations
    IEC
    Power loss (W)
    109
    Resistance (ohm)
    0,0087
    Min breaking current I3(A)
    320

    Accessories

    Product added to wishlist